Local Controls: Mount - AUMA AMB 01.1 Manual

Part-turn actuators
Table of Contents

Advertisement

Commissioning
controls settings
10.4.

Local controls: mount

40
1.
Loosen all 3 screws [2] on the signal and control board [1] and remove board.
Information: Make sure not to disconnect the jumpers.
Figure 29: Remove signal and control board
2.
Set push-to-run operation or self-retaining via red jumper on wiring board.
Link via B1 = self-retaining REMOTE
Link via B2 = push-to-run operation REMOTE (continuous signal RE-
MOTE)
Figure 30: Wiring board
3.
Fasten signal and control board [2] again.
1.
Clean sealing faces of housing and cover.
2.
Check whether O-ring [3] is in good condition, replace if damaged.
3.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
Figure 31:
4.
Fit local controls [1].
SQ 05.2
SQ 14.2/SQR 05.2
SQR 14.2
AMB 01.1