Circutor Computer SMART III FAST 12Vdc Instruction Manual page 80

Reactive energy regulator
Table of Contents

Advertisement

in which case the C/K value of the previous example would be 0.72.
Press the
digits to be modified.
The
key increases the digit value.
The
key decreases the digit value.
The
Press
Minimum value: 0.02
Maximum value: 1.0
If the value entered is lower than the minimum value or higher than the maximum value, the backlight
of the display flashes and the value entered is replaced with the minimum or maximum value, or with
the last value validated.
Press the
If no keys are pressed for 5 minutes, the unit switches to the simulation screen,
.
SCREEN"
80
If the C/K is configured lower than the actual value, connections and disconnections
would occur continuously with few load variations (the system performs more opera-
tions than necessary).
If the C/K is configured higher, the regulator requires a higher demand for reactive
power in order to switch and perform fewer operations.
key to enter editing mode. It is identified by the
key skips to the previous digit and the
to validate the data; the
key to access the next programming step.
key skips to the next digit.
symbol disappears from the display.
Computer SMART III FAST 12Vdc
symbol and the blinking of the
"5.29.- SIMULATION
Instruction Manual