The holding force of the locking magnet is tested on power-up. If the magnet's holding
force is not achieved after max. 600 ms, there will be no switch from low to high. The
holding force will be tested a further 7 times.
These tests have no influence on the signal output. If the test is successful during any
of these attempts, the gate is locked.
}
After S31 switches to low, wait at least 500 ms until S31 is switched back to high. Also
note the max. switching frequency (see Technical details:
actuator [
}
For physical reasons, a remanence (residual magnetism) remains after the locking
magnet is switched off; this is dissipated the first time the sensor and actuator are sep-
arated. Therefore a higher effort is required when opening for the first time.
}
If the safety gate is in a locked condition and is opened by force, the safety outputs will
shut down.

Lateral and vertical offset

}
Max. vertical offset 5 mm
}
Max. lateral offset: 3 mm

Wiring

Please note:
}
You must comply with the specifications stated in the technical details (see Technical
details:
actuator [
Operating Manual PSEN sl-1.0p 3.1
1003389-EN-04
25],
System with free-moving actuator [
System with normal actuator [
28]).
System with normal
28], under electrical data).
25],
System with free-moving
11