Power supply's +24 V must be grounded.
Wiring must not be bent, cracked, nor damaged.
Operation check while the machine is stopped
The test rod is not deformed.
Use a test rod with an appropriate diameter for inspection.
The sensor can detect a test rod wherever it is in the detection zone. In other words, when a test rod
is inserted into the detection zone, the stable-state indicators (STB) turn off and the ON/OFF output-
state indicators turn red.
When the external test function is used:
ON/OFF-state indicators turn red when the test input line is short-circuited to 0 V to 3 V.
When the external device monitoring function is used:
When the F3SJ-B is blocked and the external device monitoring input terminal is open, it enters a
lockout state.
When the manual reset function is used:
After the F3SJ-B is turned ON, the ON/OFF-state indicators must remain red, even if the F3SJ-B is
not blocked. The reset input must turn the ON/OFF-state indicators to green.
After that, when the F3SJ-B is blocked and returned to unblocked state when the ON/OFF-state
indicators are green, the ON/OFF-state indicators remain red. The reset input must turn the ON/OFF-
state indicators to green.
When using muting lamp:
Under muting state, a signal that indicates muting state is output to the auxiliary output.
Under override state, a signal that indicates override state is output to the auxiliary output.
Checking that hazardous parts stop while the machine operates
The hazardous parts stop immediately when a test rod is inserted into the detection zone at three
positions: "directly in front of the emitter", "directly in front of the receiver", and "between the emitter
and receiver". (Use the appropriate test rod.)
The hazardous parts remain stopped as long as the test rod is in the detection zone.
The hazardous parts stop when the power of the F3SJ-E/B is turned OFF.
The actual response time of the whole machine is equal to or less than the calculated value.
Start
Stop
Checklists
E
F3SJ-E/B
107
User's Manual