10 To reduce heat output, turn Hi/Lo Knob counterclockwise to desired temperature (see Figure 5-1 Gas Valve). Blower speed
can also be turned down to reduce heat distribution.
NEVER "over fire" by increasing BTUH above nameplate specifications.
NEVER turn down (reduce) pilot flame below the minimum 325 millivolts.
11 Open windows for first two hours of operation.
NOTICE: Initial start-up will cause some NON-TOXIC "off gassing" of adhesives, binders, paint, etc. Most
nuisance odors will be
eliminated after the first 2 hrs. of operation, however, slight amounts may be present during the first 24
hrs.
5.5 TO TURN OFF GAS TO FIREPLACE
1.
Turn "OFF" the wall thermostat, wall switch, timer or any other fireplace control device. Pilot will remain lit for return to
normal service.
2. For complete shutdown turn Gas Cock Dial to "OFF".
3.
Turn off the internal manual shutoff valve in the appliance. See 3.4.6 Factory Installed Manual Gas Shutoff Valve.
85-03-01116