Mendota AA-11-00392 Installation And Operating Instructions Manual page 20

Timberfire direct vent gas fireplace heater
Table of Contents

Advertisement

Rough Framing Dimensions
The rough framing dimensions given are the
minimum allowed framing dimensions. Be sure
when planning the framing of the unit that
adequate paths to route the gas and electrical are
available on both sides of the unit.
SPECIAL FRAMING NOTE:
If the fireplace is to be recessed in a cavity deeper
than 16", all framing and finishing materials
protruding past the front face of this fireplace
must be of the NON-COMBUSTIBLE variety.
MINIMUM FRAMING DIMENSIONS
WIDTH = 41"
HEIGHT = 33"
Combustible mantels are not allowed below 30-1/4" from
floor level of this fireplace. The mantel chart starts at 30-1/4"
above floor level.
If the mantel is constructed of non combustible materials, it may be placed at any distance above the top air gap.
Caution: Materials made of porous stones or sedimentary rocks may crack due to expansion of the material if placed around this
appliance. Use suitable materials which are crack resistant and high temperature resistant.
85-03-01116
DEPTH = 16"
Figure 3-17
Minimum Required Rough Framing Dimensions
DESCRIPTION
A
WIDTH
B
HEIGHT
C
DEPTH
E
FINISH MATERIAL THICKNESS
UNIT BASE TO ENCLOSURE
F
CEILING
GLASS FRAME EDGE TO SIDE
G
WALL
H
UNIT BASE TO 8" MANTEL
DXV42 TIMBERFIRE
DIMENSION
(INCHES)
41"
33"
16"
Varies
58-1/4""
12"
31-1/4"
Figure 3-18
Page 20