Clearance Requirements
Clearance from Appliance Body and Vent
Figure 3-20 CLEARANCES TO BODY & VENT
Figure 3-21 CLEARANCES TO VENT
The required clearances are depicted in these diagrams.
1. Minimum Clearance from fireplace body sides to combustibles is ¼".
2. Minimum Clearance from fireplace top surface to combustibles is 2" or ¾" from top edge of top triangle standoffs.
3. Minimum Clearance from vertical vent pipe sides to combustibles is 1".
4. Minimum Clearance below horizontal vent pipe or components is 1".
5. Minimum Clearance above elbows and horizontal vent pipe and components is 2".
Page 22