Mendota AA-11-00392 Installation And Operating Instructions Manual page 57

Timberfire direct vent gas fireplace heater
Table of Contents

Advertisement

Figure 4-12 MINIMUM RISE HORIZONTAL VENT
6. Note: Combustible wall thickness must be 4" to 8" maximum for wall thimbles to work properly as designed.
Note: Do not separate telescoping section. They be must be used as complete assemblies.
7. From the exterior of the home, slide the horizontal vent cap over the end of the horizontal pipe and tightly secure the vent cap
to the wall with screws. Seal with high-quality caulking around the outer perimeter of the vent cap.
Note: Vent cap shall not be recessed into wall or siding.
Elevated Vertical Rise Through-The-Wall Venting
The required MINIMUM vertical rise is 48 in. when used with a maximum horizontal run of 12 ft. For other venting configurations
within these maximum limits.
NOTE: All horizontal runs of vent pipe must be level or have a ¼" rise for every 1' of run toward the termination. Never allow the
vent to run downward. This will cause high temperatures and the possibility of a fire.
USING OFFSETS AND RETURNS: A single 90º vertical-to-horizontal elbow is already calculated into the allowable maximum 12'
horizontal run. Each additional 90º elbow reduces the maximum horizontal distance by 3'. Example: by using three total 90º
elbows the maximum horizontal distance has been reduced to 6 ft. (3 - 1 = 2 elbows x 3' = 6'; 12' Max. - 6' of elbows = 6' of
horizontal run). Note: 45º elbows reduce the maximum horizontal distance by 1½ '.
SUPPORT: Horizontal runs of pipe will require one vent support for every 3 ft. of pipe.
CAUTION: If a vertical-to-horizontal elbow is enclosed within a wall, floor or ceiling, a top air space clearance of 2" must be
maintained above the elbow. Be sure to maintain 1" air space to any combustibles on the sides and bottom, 2" above horizontal
pipe sections.
THIS FIREPLACE MUST BE INSTALLED BY A QUALIFIED MENDOTA APPROVED SERVICEPERSON.
1.
Position fireplace in desired location. Check to determine if wall studs are in the way when vent system is attached. If this is
the case you may want to adjust the fireplace location.
2.
Locate the position where vent pipe will pass through any ceilings and will penetrate the outside wall. Since vent pipe
sections "overlap" we suggest pre-assembling and measuring the total vent pipe run so you can more accurately locate the
point where the vent pipe will penetrate the outside wall Be sure all vent components are properly twist locked and leak-
proof.
85-03-01116
DXV42 TIMBERFIRE
Page 57