Mendota AA-11-00392 Installation And Operating Instructions Manual page 24

Timberfire direct vent gas fireplace heater
Table of Contents

Advertisement

Clearances to Combustible Mantels
An 8" combustible mantel may be installed at a minimum of 9" above the top of the heat outlet (38-1/4" up from the floor level
of this Fireplace). Non-combustible (marble, brick, stone, metal etc.) mantels can be installed at any desired height above the
top convection air opening. Any pre-existing combustible mantel must fall within the approved mantel profile chart.
WARNING: Make proper use of this chart. Do not compromise the specifications contained in this chart.
Failure to adhere to proper clearances required to combustibles may cause spontaneous combustion of the mantel and may
result in a fire causing property damage, personal injury or loss of life.
NOTE: For mantels that protrude more than 8 inches from the front surface of the fireplace use a rise and run of (1:1) to
calculate the required height to the mantel. EXAMPLE: You have a 12" mantel. To calculate the height above the
convection air opening the equation would be: 12" x (1/1) +1 = 13" above the convection air opening. DO NOT deviate from
this minimum clearance requirement. Doing so can lead to a severe fire hazard.
Note: The distance from the Floor Level of this Fireplace to the top of the Top Air Gap is 29-1/4". Combustible
mantels cannot be installed below 30-1/4" height from floor level of this fireplace.
85-03-01116
Figure 3-22 Mantel Clearances
Figure 3-23 Mantel Clearances
DXV42 TIMBERFIRE
Page 24