Wiring; Settings - Omron E5EZ-PRR User Manual

Position proportional controller
Hide thumbs Also See for E5EZ-PRR:
Table of Contents

Advertisement

Chapter 3 Basic Operations

■ Wiring

■ Settings

in-t
5
l.ini
3-18
Input should be connected to terminals 9, 10, and 11 depending on input type.
The OUT1 terminal links to the position proportional valve OPEN side and the
OUT2 terminal to the CLOSE side.
ceramic kiln
(combustion)
Sensor
Combustion device
Use position proportional control type position proportional valves, with travel
time (from fully closed to fully open) at 45 seconds to floating control. And use
the SP ramp function at 10.0°C/minute to gradually change the present value.
Related setting data and information are given below:
「Direct Reverse
Operation」
「Closed/floating」
「Travel time」
「SP ramp Set Point」
Travel time and SP ramp set point are set, other parameters use the initial
values.
for 3 or more seconds, and from the "operation level" access
(1) Press the key
the "initial settings level".
C
W O
CLOSE
OPEN
VALVE
Position Proportional Valve
= 「or-r: Reverse Operation」 (initial value)
= 「flot: Floating」 (initial value)
"
"
=
45
second
"
"
=
10