Chapter 4 Applied Operations

■ Settings

● Setting Set
Point Upper
Limit
Operation
Procedure
Initial Setting Level
Input Type
in-t
5
l. ini
Setting
C
sl-h
Upper Limit
1300
l. ini
C
sl-h
1000
l. ini
● Setting Set
Point Lower
Limit
Operation
Procedure
Set Point
C
5l-l
Lower Limiit
-200
l. ini
C
5l-l
-100
l. ini
4-16
By setting the "set point upper limit"and "set point lower limit" parameters in the
"initial level", the set points upper and lower lower limit values can be set. This
example describes how to set "-200°C ~ 1300°C" range K type thermocouple
input limit settings at "-100°C ~ 1000°C".
Set the "set point upper limit" parameter to "1000".
key for 3 seconds or more, switch from the "initial level" to the
(1) Press the
"operations level".
"
(2) Select
set point upper limit
(3) Use the UD key to set the parameter to
Set the "set point lower limit" parameter to "-100".
(1) In the "initial level" select "set point lower limit".
(2) Use the UD key to set the parameter to
Sensor Range
Setting Limiter
"
.
"
"
1000
.
"
"
-100
.