Switching To The Advanced Function Level - Omron E5EZ-PRR User Manual

Position proportional controller
Hide thumbs Also See for E5EZ-PRR:
Table of Contents

Advertisement

4.7

Switching to the Advanced Function Level

Protection Level
"Run/Adjustment
Protection"
oapt
0
l. prt
"Initial/Communications
icpt
Protection"
1
l. prt
icpt
0
l. prt
Operation Level
PV/SP/Valve Open %
c
25
100
100.0
Initial Setting Level
Input Type
in-t
5
l. ini
-169
l. ini
Advanced Function Level
Switch to Advanced
init
Function Level
off
l.

4.7 Switching to the Advanced Function Level

In the initial setting level, the advanced function level is protected and cannot
be accessed. To switch to the advanced function level, first cancel protection in
the "protection level". Please see "4.8 Using the Key Protection Level".
(1) In the "operation level", simultaneously press the
more.
* Key timing can be set using "protection level switching time" (advanced function
level) .
(2) The controller will switch to the protection level and display
adjustment protection
Press the M key once to switch to "initial/communications protection".
(3)
"
(4) Set the set point to
(5) Simultaneously press the
(6) Press the
key for 3 seconds or more to switch from the
"
"
the
initial level
.
(7) Press the M key , select thse "switch to advanced function level" parameter .
(8) Use the UD key to input the password (
2 seconds or more to switch from the
"
level
.
"
.
"
0
.
and M keys to return to the
"
-169
"
initial level
and M keys for 3 seconds or
"
operation /
"
operation level
"
operation level
"
) , then press the M key or wait
"
"
to the
advanced function
"
.
"
to
4-19