Switch List - Mitsubishi Electric PAC-YG66 DCA-J Installation Instructions Manual

Table of Contents

Advertisement

9

Switch List

Switch
Channel
SW01
1
2
Channel 1
3
(standard)
4
5
6
Unused
7
Unused
8
Unused
SW02
1
2
Channel 2
3
(standard)
4
5
6
Unused
7
Unused
8
Unused
SW03
1
2
Channel 3 to 6
3
(standard)
4
5
Selection of status display mode:
6
(1) Normal display (input status or error status
of channels 1 and 2):
(2) Operation input status display of channels 3 to 6:
(3) Operation output status display of channels 3 to 6:
7
(4) Error input status display of channels 3 to 6:
8
Error display is cancelled (for 10 seconds).
SW06
M-NET address
SW07
SW08
Channel 1
1
(standard)
Channel 2
2
(standard)
Channel 3
3
(expansion)
Channel 4
4
(expansion)
Channel 5
5
(expansion)
Channel 6
6
(expansion)
SW09
1
Unused
2
Unused
Set the dip switches for function selection according to the system to be used.
At the time of shipment, all dip switches are set to OFF and the M-NET address is set to 01.
The settings of SW03-1 to 5 are common to expansion input/output channels 3 to 6.
Function Setting
Emergency stop command
enable setting
Error input logic setting
Error interlock stop output
setting
Output operation setting for
power failure recovery
Output method setting
Emergency stop command
enable setting
Error input logic setting
Error interlock stop output
setting
Output operation setting for
power failure recovery
Output method setting
Emergency stop command
enable setting
Error input logic setting
Error interlock stop output
setting
Output operation setting for
power failure recovery
Output signal setting
Error input usage setting
OFF
ON
Disabled
Enabled
a contact
b contact
No
Yes
Recover to
Stop
state prior to
power failure
Level output
Pulse output
Disabled
Enabled
a contact
b contact
No
Yes
Recover to
Stop
state prior to
power failure
Level output
Pulse output
Disabled
Enabled
a contact
b contact
No
Yes
Recover to
Stop
state prior to
power failure
Level output
Pulse output
SW03-6,
SW03-7
OFF
OFF
OFF
ON
ON
OFF
ON
ON
Change the switch to ON once
and then return it to OFF.
(Address 10s) 0 to 9 (decimal)
(Address 1s) 0 to 9 (decimal)
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
12
Remark
Select the output operation for when an emergency
stop command is received from a system
controller.
Select whether to interlock and stop output for error
input.
Select the output operation for when there is a
recovery from a power failure.
Set to OFF
Set to OFF
Set to OFF
Select the output operation for when an emergency
stop command is received from a system
controller.
Select whether to interlock and stop output for error
input.
Select the output operation for when there is a
recovery from a power failure.
Set to OFF
Set to OFF
Set to OFF
Select the output operation for when an emergency
stop command is received from a system
controller.
Select whether to interlock and stop output for error
input.
Select the output operation for when there is a
recovery from a power failure.
Select the display mode for the status display LED
mode.
Only enabled while communication error status is
displayed.
* The communication error status display is
masked for 10 seconds and the status set with
SW03-6 and 7 is displayed.
An address from 01 to 50 can be set.
Set an address that is not the same as that of
another unit.
Select whether to use error/normal input for
channel 1.
Select whether to use error/normal input for
channel 2.
Select whether to use error/normal input for
channel 3.
Select whether to use error/normal input for
channel 4.
Select whether to use error/normal input for
channel 5.
Select whether to use error/normal input for
channel 6.
Set to OFF
Set to OFF