(b) Transistor Outputs (Open Collector)
* To use these, various settings need to be configured. Refer to "8 Initial Setting Procedure".
24 VDC
Power
source
FG
Line Onsite
CN16
V+/ V-/ FG
24 VDC Power source
Tightening torque for terminal screws: 1 N·m
Note: The junction terminal CN40 is provided.
Use them as relay terminals if necessary.
X1
Ch1
/
CN06
CN40
ON/OFF,
(ON)
( ) is in the case of a pulse.
X2
Y1
Y2
Ch2
/
/
05
08
03
ON/OFF,
(OFF)
(ON)
(OFF)
9
Caution:
• When X1, X2, Y1 and Y2 relays are
used, select ones that satisfy the
following specifications.
Operating coil
Rated voltage: 24 VDC (Built-in
diode)
Power consumption: 0.9 W or less
(*1) Be sure to use the ones with
the voltages rated above.
Exceeding the rated voltage
may affect the ON/OFF of
other outputs.
(*2) When using a separate
power supply for this device,
connect GND of the power
supply to V- of CN16 of the
terminal block of this device.
(*3) Use a relay with a
withstanding voltage of at
least 2000 VAC between the
coil and contact.
Otherwise, there is the
likelihood of an electric shock
or fire.
• Strip 12±1 mm (15/32 ±1/32 in) of the
wire coating and insert firmly into the
terminal.
• Make sure that the copper wiring is
not short-circuiting the plates (cover,
lower case) or neighboring wires.
• Perform wiring so that the terminal
block is not strained.
If strained, use a wire guide or
junction terminal to alleviate the
stress on the terminal block.
• Do not connect the wires directly from
the top of the control panel to the
terminal block.
Moisture may enter this device along
the wiring and cause electric shock or
fire.