Initial Setting Procedure - Mitsubishi Electric PAC-YG66 DCA-J Installation Instructions Manual

Table of Contents

Advertisement

8

Initial Setting Procedure

After completing the procedures described in "6 Installation Method" and "7 Wiring Method," set the initial settings in
accordance with the procedure described below.
(1) M-NET address settings
In the case of address "41"
(2) Use the dip switches to select functions.
Select the function required for each input/output channel to be used.
The switch assignment for each channel is shown below. Configure each of the settings while referring to "9 Switch List".
Setting
Emergency stop command enable setting
Error input logic setting
Error interlock stop output setting
Output operation setting for power failure recovery
Output signal setting
Selection of status display mode
Error display is cancelled (for 10 seconds).
Error input usage setting
(3) Turn on the power of this device.
Verify that the LED16 (CPU power on) and LED17 (M-NET power on) are lit.
(4) Set the group settings so that this device is a target for control from the system controllers.
Set the group settings (contact numbers to use (channel)) in the system controllers (G(B)-50A, TG-2000A, system remote controller,
schedule timer, and ON/OFF remote controller) and then start up this device.
* With the system remote controller, schedule timer, and ON/OFF remote controller, group settings can only be configured for
channel 1.
(5) Set the time.
Set the current time from a system controller (G(B)-50A, TG-2000A, system remote controller, or schedule timer) or a Maintenance
Tool.
(6) To use the interlock control function, perform settings from the Maintenance Tool.
Perform settings such as interlocking criteria for this device with the Maintenance Tool.
For details on setting procedures, refer to the instruction manual for the Maintenance Tool.
10s
1s
SW06
SW07
Note:
• An address from 01 to 50 can be set.
• Set an address that is not the same as that of
another unit.
The address is set to "01" at factory shipment.
Standard
Ch1
Ch2
SW01-1
SW02-1
SW01-2
SW02-2
SW01-3
SW02-3
SW01-4
SW02-4
SW01-5
SW02-5
SW03-8
SW08-1
SW08-2
11
Channel Used
Expansion
Ch3
Ch4
SW03-1 (The setting is common to channels 3 to 6)
SW03-2 (The setting is common to channels 3 to 6)
SW03-3 (The setting is common to channels 3 to 6)
SW03-4 (The setting is common to channels 3 to 6)
SW03-5 (The setting is common to channels 3 to 6)
SW03-6, SW03-7
SW08-3
SW08-4
Ch5
Ch6
SW08-5
SW08-6

Advertisement