7 Diagnostics and servicing
26
13. Check the hold of the wires in the terminals by lightly pulling on
them
14. Check cable gland on tightness. The seal ring must completely
encircle the cable.
15. Mount the probe into the vessel. Make sure that the probe is
uncovered.
2
Fig. 18: Compensation key
1
Measuring range selection switch (compensation key)
2
Control lamp
16. Keep the measuring range selection switch (1) pushed until the
control lamp (2) flashes green.
17. Carry out the adjustment again. See chapter " Set-up, adjustment
elements".
18. Screw the housing lid back on
The electronics exchange is now finished.
7.4

Shortening of the probe

The probe can be shortened by any amount.
1. Loosen the two pins on the gravity weight (hexagon) and remove
the pins.
2. Pull the cable out of the gravity weight.
3. To avoid splicing of the steel cable, tin the cable before shortening
with a soldering iron and tighten the wire.
4. Shorten the cable with a cut-off wheel or metal saw at the lower
end. Make sure the length is correct before shortening.
1
VEGACAP 65 • Two-wire