Vega VEGACAP 65 Operating Instructions Manual page 22

Capacitive cable electrode for level detection
Table of Contents

Advertisement

6 Setup
Measuring range selec-
tion switch (1)
Signal lamp (4)
Switching point adjust-
ment
22
With the potentiometer on the controller and the measuring range
selection switch (1) on VEGACAP 65 you can change the sensitivity
of the probe to the electrical properties of the product and the condi-
tions in the vessel. This is necessary so that the level switch can also
reliably detect products e.g. with very low or very high dielectric figure.
range 1: 0 ... 20 pF
Range 2: 0 ... 85 pF
Range 3: 0 ... 450 pF
Control lamp for indication of the device status.
green = instrument functions
red (flashing) = failure
See operating instructions manual of the " Controller".
The adjustment of the switching point is only possible in installed
condition.
Standing capacitances in a vessel can influence the measurement.
We therefore recommend to carry out a compensation of these stand-
ing capacitances before the adjustment.
1. Make sure that the probe is correctly mounted and connected.
2. Make sure that the probe is uncovered.
2
Fig. 15: Compensation key
1
Measuring range selection switch (compensation key)
2
Control lamp
3. Keep the measuring range selection switch (1) pushed until the
control lamp (2) flashes green.
4. Then carry out the adjustment.
The detailed adjustment of VEGACAP 65 is described in the operat-
ing instructions manual of the " Controller".
1
VEGACAP 65 • Two-wire