Technical Specifications - Presys DMY-2030-F Technical Manual

Frequency digital indicator
Table of Contents

Advertisement

PRESYS
⏐ Instruments
Field E
1
2
3
Field F
0
1
2
3
Field G
0
1
2
Note 1 - The input ranges, indication, relay usage as alarms and the alarm points
are, among other things, items that the user can program through the front keys (if
wanted, specify this information so that all the configuration can be made by PRESYS).
Note 2 - Other hardware and software features are available under previous
consult.
Code Example:
1) DMY - 2030 - F - 0 - 0 - 1 - 1 - 1 - 0 - 0
This code defines a DMY-2030-F Indicator with two SPDT relays which can be
used as high and low alarms, 90 to 240 Vac or 130 to 340 Vdc electric power supply,
protected field usage.

1.3 - Technical Specifications

Inputs:
• Two frequency inputs (DMY-2030-F) or one frequency input
(DMY-2030-F Light) for connection of frequency signals of sinusoidal, or
triangular waveforms, pulses with amplitude between 300 mV
30 V
p-p
impedance greater than 60 kΩ (sinusoidal, 1 kHz). Table 1 shows reading
accuracy and display resolution according to frequency range.
Frequency Range
0.0000 Hz - 3.0000 Hz
0.000 Hz - 30.000 Hz
0.00 Hz - 300.00 Hz
0.0Hz - 3000.0Hz
0Hz - 30000Hz
Power Supply
90 to 240 Vac or 130 to 340 Vdc (any polarity)
24 Vdc
12 Vdc
Communication
Not used
RS-232
RS-485
RS-422
Case Protection Grade
General usage, protected place
Front aspersion-proof
Weather-proof
and input form contact closures. 70 V maximum DC voltage. Input
Accuracy
0.0002 Hz
0.002 Hz
0.02 Hz
Table 1 - Reading accuracy and resolution.
DMY-2030-F / DMY-2030-F Light
0.2Hz
2Hz
and
p-p
Resolution
0.0001 Hz
0.001 Hz
0.01 Hz
0.1Hz
1Hz