Presys DMY-2030-F Technical Manual page 32

Frequency digital indicator
Table of Contents

Advertisement

PRESYS
⏐ Instruments
Outputs 1 and 2 as retransmitter outputs (optional module code: MSAN-20)
When output 1 is required to be a retransmitter output (4 to 20mA, 1 to 5V or 0 to
10V), connect the optional analog output module in the connector called MOD 1. If
another retransmitter output is needed, connect the second module in the connector
called MOD 2.
The output 1 retransmits the measured variable from input 1 while output 2
retransmits the measured variable from input 2.
The optional analog output module has two connectors for installation of jumpers:
J1 and J 2, as shown in Figure 21.
In order to configure the optional analog output module as a retransmitter output
for 4 to 20mA, 1 to 5V or 0 to 10V, install the jumper according to table 2.
Retransmitter Output Type
4 to 20mA*
1 to 5V
0 to 10V
Table 2 - Jumper for retransmitter output type configuration
(*) In case of 4 to 20mA current retransmitter output, keep the jumper out of the
instrument or put it on only one pin of the connector, as shown in Figure 17.
Outputs 1 and 2 as alarm outputs
If output 1 or output 2 is required to operate as alarm, connect the optional
module in the connectors called MOD 1 and MOD 2, respectively. The output type
depends on the optional module installed in MOD 1 and MOD 2: SPST relay, the solid
state relay and the open collector voltage. The alarm output type and the optional
module code are listed in table 3.
Fig. 21 - Place of jumpers in analog output board
DMY-2030-F / DMY-2030-F Light
Locations of Jumpers 1 and 2
Jumpers
J1
J2
Maintenance
Page 29