Chapter 8: Specifications
SYSTEM SPECIFICATIONS
Model Number
EN450G
Topology
Maximum Power Capacity
Number of Phase
Nominal Voltage
Acceptable Input voltage
Voltage Range
Frequency Limits
Low Voltage Transfer Point
High Voltage Transfer Point
140V resets to Utility Power at 136V or lower
Input Protection
OUTPUT NON-BATTERY OPERATION
Voltage Range
Voltage Regulation
Frequency Range
Efficiency (Line Mode)
OUTPUT BATTERY OPERATION
Waveform Type
Nominal Voltage
Voltage Regulation
Frequency
60Hz, ±0.5Hz (unless synchronized to utility)
Transfer Time
AC Mode: 105% for 1-minute then shutdown,
115% Shutdown Immediately
Overload Capacity
DC Mode: 105% for 20-seconds then shutdown,
115% Shutdown Immediately
Protection
Over-Current, Short-Circuit Protected, Latching Shutdown
REGULATORY COMPLIANCE
cTUVus (Conforms to UL1778 5th Edition & CSA 22.2 no.
Safety and Approvals
107.3:2014/R:2017-10), FCC Class B, CE certified,
RoHS2 (EU Directive 2011/65/EU & 2015/863/EU)
30
EN600GU
Standby, Simulated Sine Wave
450VA
600VA
250W
330W
INPUT
Single (1Ø 2W +G)
120VAC
0 - 150VAC
95 - 140VAC
60 Hz, ±6Hz
95V resets to Utility Power at 99V or higher
Resettable Circuit Breaker
95 - 140VAC
120VAC: -20.8% - +16.7%
60Hz: 54 - 66Hz
>98% (Full Load)
Simulated Sine Wave
120VAC
Nominal ±5% (until Low Battery Warning)
6 ms Typical
Battery Type
Typical Recharge Time
EN750G
Typical Battery Life
750VA
Battery Module Part #
450W
Runtime: Full Load (minutes)
Runtime: Half Load (minutes)
Surge Energy Rating
Surge Current Capability
Surge Response Time
Surge voltage let-through (as
a percentage of an applied
ANSI C62.41 Cat. A ±2 kV)
Noise Filter
Audible Noise at 1 m (3 ft.)
Operating Temperature
Operating Elevation
Operating/Storage Humidity
Storage Temperature
Storage Elevation
Size - Net
L X W X H
Weight - Net
Size - Shipping
L X W X H
Weight - Shipping
Power Cord
Output Receptacles
Qty / Type / Voltage / Current
Specifications are subject to change without prior notice.
BATTERY SYSTEM
Sealed, Non-Spillable, Maintenance Free,
Value Regulated, Lead Acid
8-hours to 90% capacity from a full load discharge
3 to 5 years. Environmental factors do affect battery life.
High temperatures, poor utility power, and frequent, short
duration discharges have a negative impact on battery life.
BM0094
2
10
SURGE PROTECTION AND FILTERING
6,500 Amps total (one time 8 to 20us waveform) 
0 ns (instantaneous) normal mode; <5 ns common mode
>45db normal and common mode EMI/RFI suppression
<45 dBA
ENVIRONMENTAL
0 to 40C (+32 to +104F)
0 to 3000m (0 to +10,000 ft)
0 to 95% non-condensing
-15 to +45C (+5 to +113F)
0 to 15,000m (0 to +50,000 ft)
PHYSICAL
12.8 x 5.7 x 4.1"
324 x 145 x 103 mm
7.3 lbs
3.3 Kgs
14.9 x 5.8 x 9.0"
378 x 147 x 227 mm
8.4 lbs
3.8 Kgs
5 ft. w/5-15P
4 - Battery Backup & Surge
4 – Surge Only
USB CHARGING PORTS EN600GU ONLY
Two (2) / Type 'A' / 5Volts / 3Amps max total
BM0095
3
11
1000 J
<5%
12.8 x 7.8 x 4.1"
324 x 198 x 103 mm
9.9 lbs
4.5 Kgs
15.2 x 5.8 x 10.9"
386 x 147 x 276 mm
10.8 lbs
4.9 Kgs
5 - Battery Backup & Surge
5 – Surge Only