Specifications - Para systems Minuteman ED10000T User Manual

Minuteman parallel redundant on-line series
Table of Contents

Advertisement

8 Specifications

MODEL
(Has an internal Galvanic
Topology
Maximum Power Capacity
INPUT
Number of Phases
Nominal Voltage
Acceptable Input Voltage
Voltage Range
Power Factor Correction
Frequency Limits
Low Voltage Transfer Point
High Voltage Transfer Point
Protection
OUTPUT
Waveform Type
Nominal Voltage
Voltage Regulation
Frequency
50/60Hz +/-0.2Hz (unless synchronized to utility)
Voltage T.H.D.
Dynamic Response
Transfer Time
Slew Rate
Efficiency (Line Mode)
Crest Factor
Overload Capacity
Protection
Over-Current, Short-Circuit and Latching Shutdown
SURGE PROTECTION AND FILTERING
Surge Energy Rating
Surge Energy Capability
Surge voltage let-through (as a
percentage of an applied ANSI
C62.41 Cat. A +/-6KV)
Noise Filter
Audible Noise at 1 m (3 ft.)
* 160 – 280VAC at loads <50% of the rated capacity
* 175 – 280VAC at loads <75% of the rated capacity
* 180 – 280VAC at loads >75% of the rated capacity
ED10000T
ED10200T
isolation step-down
transformer)
Double Conversion On-Line, True Sine Wave
10000VA/7000Watts
Single (1Ø 2W +G)
208VAC
0 - 300VAC
160* - 280VAC
>98% at Full Load
50/60Hz +/-5Hz autosensing
160V resets to utility power at 175V or higher
280V resets to utility power at 265V or lower
Re-settable Circuit Breaker
True Sine Wave
120VAC and
208/240VAC
208/240VAC
+/-2% (until Low Battery Warning)
<3% (Linear load)
+/-5% @ 100% Load change in 100ms
0ms
<1Hz / second
>87% (Full Load)
3 : 1
>105% - <155% for 160 seconds
>156% shutdown immediately
1050 J
6500 Amps total
<5%
Normal and common mode EMI/RFI suppression
<50dB
38
BATTERY
Type
Typical Recharge Time
3 - 5 years, depending on the number of charge
Typical Battery Life
and discharge cycles, and ambient temperature
System Voltage
Quantity/Rating
Battery part numbers
Runtime (full/half load)
ENVIRONMENTAL
0 to 40ºC (+32 to +104ºF) <2000m (<+6700 ft)
Operating Temp (max)
0 to 35ºC (+32 to +95ºF) at 3000m (+10,000 ft)
Storage Temp
Operating/Storage Humidity
Storage Elevation
PHYSICAL
Size - Net
D x W x H
645 x 290 x 881mm
Weight - Net
Size – Shipping
D x W x H
810 x 468 x 1110mm
Weight - Shipping
REGULATORY COMPLIANCE
UL 1778, cUL (CSA 22.2 no. 107.1), CE
Safety and Approvals
(EN62040-1-1)
CE (EN62040-2, EN61000-3-2, EN61000-3-3),
EMC
FCC Class A
Sealed, Non-Spillable, Maintenance Free,
Valve Regulated, Lead Acid
8-hours from total discharge
240VDC
20-12V9Ah
Yuasa – NPW45-12
CSB – HR 1234W F2
Panasonic – LC-R129
5/15 minutes
-15 to +45ºC (+5 to +113ºF)
30 - 90% Non-Condensing
0 to 15,000m (0 to +50,000 ft)
25.4 x 11.4 x 34.7"
25.4 x 11.4 x 29.4"
645 x 290 x 748mm
374 lbs
264 lbs
170 kgs
120 kgs
31.9 x 18.4 x 43.7"
31.9 x 18.4 x 38.5"
810 x 468 x 977mm
412 lbs
302 lbs
187 kgs
137 kgs
39

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Minuteman ed10200t

Table of Contents