MODEL #
RATED OUTPUT
(WATTS)
MM450
MM850
MM1300
MM2000
*MM2000
MM2000/2
MM2000/2U
* MM2000 Specifications if optional 5-15P plug is used.
MM2000/2U available in both 208VAC and 240VAC models.
Input Voltage (AC Mode Function) .................
Input Frequency Deviation for Synchronization.
Inrush Current ...........................................
Surge Protection ........................................
RFI/EMI/Noise Filtering ................................
Transfer ...................................................
Brownout Transfer .................................
AC Return ............................................
Transfer Speed .....................................
Inverter Mode (Backup Operation)
Waveform ............................................
Crest Factor (Non-Linear Mode) ...............
Overload Capacity (50mSEC Maximum) ....
Voltage Regulation ................................
Frequency Regulation ............................
DC-to-AC Efficiency (Full Load) ...............
Overload/Short Circuit Protection .............
Discharged Battery Recharge Time ..........
Run Time .............................................

ELECTRICAL SPECIFICATIONS

FREQ
(Hz)
315
60
600
60
900
60
1400
60
1400
60
1400
50
1400
60
1400
60
INPUT
OUTPUT
(VAC/A)
(VAC/A)
120/3.9
120/2.6
120/7.1
120/5.0
120/10.8
120/7.6
120/16.6
120/11.7
120/12.0
120/11.7
220/9.2
220/6.4
208/9.6
208/6.7
240/8.3
240/5.8
120VAC ± 15VAC; 220VAC ± 30VAC
± 5%
1.5x Rated
3-way, meets IEEE STD 587
Both Common and Normal Modes
120VAC UNITS
102VAC
107VAC
Synchronized Sinewave
3:1
3x Rated
± 5%
± 1%
70%
Electronic and Fused
8 Hours (95% of Full Charge)
See Chart and Graphs
4
BATTERY SYSTEM
(VDC)
24 (INT)
48 (INT)
48 (BP)
48 (BP)
48 (BP)
48 (BP)
48 (BP)
48 (BP)
220VAC UNITS
190VAC
200VAC
2ms Typical

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mm850Mm1300Mm2000

Table of Contents