NOTE: Use Caution, the battery module is heavy.
11. Slide the new battery module into the UPS.
12.Verify proper polarity. Reconnect the battery connectors (red and black).
NOTE: Some sparking may occur this is normal.
13.Place the battery connectors in the battery connector holder and then lock
in place.
14.Re-install the battery retaining bracket.
15.Re-install the battery door on the UPS.
16.Connect the computer interface cable to the rear panel of the UPS.
17 Connect the equipment to the output receptacles of the UPS.
18.Connect the UPS's AC power cord to the AC wall outlet.
19.Press and release the ON button on the front panel to turn the UPS On.
20.Turn on the equipment that is plugged into the output receptacles of the
UPS.
21.The UPS is now ready for the normal operation.
22.Properly dispose of the old battery module at an appropriate recycling fac-
ility or return them to the supplier in the packing material that the new batt-
ery module came in.
NOTE: If the UPS has a Weak/Bad Battery Alarm after replacing the battery
module, the user must initiate a battery test to clear the Weak/Bad Battery
Alarm. To initiate a self test see section 4 "USER INVOKED BATTERY TEST".
FIG. 3
FIG. 4
24
Chapter 9: Specifications
SYSTEM SPECIFICATIONS
EC1000RT2U
Model Number
1000VA
Maximum Power Capacity
900W
Topology
Double Conversion On-Line, True Sine Wave
Number of Phase
Nominal Voltage
Acceptable Input voltage
Voltage Range
Frequency Limits
Power Factor Correction
Low Voltage Transfer Point
55V (load dependent) resets to Utility Power at 75V or higher
High Voltage Transfer Point
150V resets to Utility Power at 145V or lower
Input Protection
OUTPUT NON-BATTERY OPERATION
Voltage Regulation
Frequency Range
Efficiency (Line Mode)
OUTPUT BATTERY OPERATION
Waveform Type
Nominal Voltage (Adjustable)
Voltage Regulation
Nominal
Frequency
50/60Hz,
Voltage T.H.D.
Dynamic Response
Transfer Time
Slew Rate
Crest Factor
>106 to <110% for 2-mins; AC mode: Transfer to Bypass, DC Mode: Shutdown
Overload Capacity
>111 to <125% for 1-min; AC mode: Transfer to Bypass, DC Mode: Shutdown
>126 to <150% for 30-secs; AC mode: Transfer to Bypass, DC Mode: Shutdown
>151% Immediately; AC mode: Transfer to Bypass, DC Mode: Shutdown
Protection
Over-Current, Short-Circuit Protected and Latching Shutdown
ECONOMY MODE OPERATION
Switches from Bypass to Inverter
Switches from Inverter to Bypass
Transfer Time
EC1500RT2U
EC2000RT2U
EC3000RT2U
2000VA
1500VA
3000VA
1350W
1800W
2700W
INPUT
Single (1∅ 2W +G)
120VAC
0 - 160VAC
55V (load dependent) - 150VAC
50 or 60 Hz,
6Hz, autosensing
±
>99% at Full Load
Resettable Circuit Breaker
Nominal
2%
±
60Hz: 54 - 66Hz or 50Hz: 44 - 56Hz
>89% (Full Load)
True Sine Wave
120VAC (110, 127VAC)
2% (until Low Battery Warning)
±
0.2Hz (unless synchronized to utility)
±
<3% (Full Linear Load)
5% @ 100% Load change in 30 ms
±
0 ms Typical
<1Hz / second
3 : 1
±15% Of the rated input voltage
Resets 10VAC from Switch Point
8 ms Typical
25