Table of Contents

Advertisement

3. Clearances to Combustible Material

The clearances shown in this section have been determined by tests according to procedures set
out in safety standards CAN/ULC S627 (Canada), UL 1482 (U.S.A.) and UL 737 (U.S.A.). When
the stove is installed so that its surfaces are at or beyond the minimum clearances specified,
combustible surfaces will not overheat under normal and even abnormal operating conditions.
No part of the stove or flue pipe may be located closer to combustibles than the minimum
clearance figures given.
Clearances may only be reduced by means approved by the regulatory authority.
The clearances to combustible walls may be slightly different in Canada and the U.S.A. and may
also differ depending on whether single or double wall flue pipe is used. Make sure to choose
the correct clearance for the stove location and type of flue pipe.
The clearances of the appliance and the flue pipes must be met individually, meaning the appliance
cannot be installed closer to the combustible materials than the single or double wall pipe allows.
For a safe way to reduce clearances refer to section"5. Reducing Wall and Ceiling Clearances Safely"
of this manual.
3.1

Clearances

APPLIANCE CLEARANCES WITH SINGLE
WALL PIPE CONNECTOR
Canada
A
14 ½" (368 mm)
B
12" (305 mm)
C
10" (254 mm)
If the above clearances are met, then the distances measured from the flue outlet will be:
DISTANCES
1
WITH SINGLE WALL PIPE CONNECTOR
Canada
D
18" (457 mm)
E
20 ¾" (527 mm)
F
19 ¾" (502 mm)
1
The pipe distances listed in this table refer to the distances obtained when the stove is installed in accordance with the appliance clearances above
mentioned.
Installation and Operation Requirements - Solution 3.3
USA
14 ½" (368 mm)
12" (305 mm)
10" (254 mm)
FROM PIPE CONNECTOR
USA
18" (457 mm)
20 ¾" (527 mm)
19 ¾" (502 mm)
APPLIANCE CLEARANCES WITH DOUBLE
WALL PIPE CONNECTOR
Canada
A
7 ½" (191 mm)
B
12" (305 mm)
C
8" (203 mm)
DISTANCES
FROM PIPE CONNECTOR
1
WITH DOUBLE WALL PIPE CONNECTORE
Canada
D
11" (279 mm)
E
20 ¾" (527 mm)
F
17 ¾" (451 mm)
USA
7 ½" (191 mm)
12" (305 mm)
8" (203 mm)
USA
11" (279 mm)
20 ¾" (527 mm)
17 ¾" (451 mm)