Enerzone SOLUTION 3.3 Owner's Manual page 17

Hide thumbs Also See for SOLUTION 3.3:
Table of Contents

Advertisement

3.1.1
With Heat Shield AC02762
To reduce the clearances of an appliance using a single wall pipe connector, the use of a heat
shield certified with the single wall pipe connector to be used as close as 6" from combustible
materials must be used. Only in this case, the same clearances as a certified double wall pipe
connector can be used. Refer to the booklet in the screen options to obtain the dimensions to
be respected.
APPLIANCE CLEARANCES WITH DOUBLE
WALL PIPE CONNECTOR
Canada
A
3" (76 mm)
B
3" (76 mm)
C
3" (76 mm)
A
D
B
E
CAN
48"
122 cm
If the clearance reduction is on the same side as the door handle, position the stove at
a minimum of 6 inches from the side wall (clearance B), otherwise it may be located at
the clearance shown in the table above.
Note that to reduce the clearances of an appliance using a single wall pipe connector, the use of a heat shield certified with the single wall pipe
1
connector to be used as close as 6" from combustible materials must be used. Only in this case, the same clearances as a certified double wall
pipe connector can be used.
2
The pipe distances listed in this table refer to the distances obtained when the stove is installed in accordance with the appliance clearances above
mentioned.
Installation and Operation Requirements - Solution 3.3
1
USA
3" (76 mm)
3" (76 mm)
3" (76 mm)
48"
US
Flush
36"
92 cm
DISTANCES
FROM DOUBLE WALL
2
PIPE CONNECTOR
Canada
D
6 ½" (165 mm)
E
11 ¾" (298 mm)
F
12 ¾" (324 mm)
F
F
USA
6 ½" (165 mm)
11 ¾" (298 mm)
12 ¾" (324 mm)
C
Page 17

Advertisement

Table of Contents
loading

This manual is also suitable for:

Eb00060

Table of Contents