gefran 800P Installation And Operation Manual page 15

Controller/programmer
Table of Contents

Advertisement

Lets you custom correct reading of the main input by setting four values: A1, B1, A2, B2.
This function is enabled by setting "Sens" +8 code ("Hrd" menu).
Example: Sens = 1+8 = 9 for RTD probe with input correction.
The scale can be reversed if this function is applied to linear scales (50mv, 10V, 20mA, Pot).
The four values are set on the "Lin" menu as follows: A1 = St100, B1 = St01, A2 = St02, B2 = St03. Setting is limited to the defined scale ("LoS"
... "HiS" on "InP" menu).
The offset function ("oFt" parameter on "InP" menu) remains enabled.
Limits:
B1 always greater than A1;
B1-A1 at least 25% of full scale of selected probe.
Example:
Sens = 9, TyPE = 0 (Pt100 natural scale -200...+600), dPS = 0
LoS = 0, HiS = 400, oFt = 0
Reference point on real curve:
Corresponding points on corrected curve: A2 = St02 = 120, B2 = St03 = 220
4
1
2
152050 9640
50 / 0.05 A
Hole for 2.9 x 9
self-threading screws
CODE
Ip / Is
Ø Secondary
TA/152 025
25 / 0.05A
0.16 mm
TA/152 050
50 / 0.05A
0.18 mm
KIT PC USB / RS485 o TTL
32
17 • MAIN INPUT CORRECTION FUNCTION
A1 = St00 = 50, B1 = St01 = 350 (B1-A1 = 300, greater than 25% of 800)
Indication
400
B2=220
170
A2 =120
A1=50
18 • ACCESSORIES
• CURRENT TRANSFORMERS
30
4
n
OUTPUTS
Ru
Wire
n
= 500
1 - 2
40 Ω
1-2
n
= 1000
1 - 2
80 Ω
1-2
• RS232 interface for instrument configuration
Kit for PC via the USB port (Windows environment) for GEFRAN instruments configuration:
Lets you read or write all of the parameters
• A single software for all models
• Easy and rapid configuration
• Saving and management of parameter recipes
• On-line trend and saving of historical data
Component Kit:
- Connection cable PC USB ... port TTL
- Connection cable PC USB ... RS485 port
- Serial line converter
- CD SW GF Express installation
GF_eXK-2-0-0
Without correction
Input
200
B1=350 400
5,5
27
5,5
2
1
2
In
8
8
38
20
Vu
ACCURACY
2 Vac
2.0 %
4 Vac
1.0 %
• ORDERING CODE
cod F049095
Whit correction
These transformers are used to measure currents
of 50 ÷ 60Hz from 25A to 600A
(nominal primary current). The peculiar
characteristic of these transformers is the high
number of secondary turns. This provides a very
low secondary current, suitable for an electronic
measurement circuit. The secondary current may
be detected as voltage on a resistor.
• ORDER CODE
IN = 50Aac
COD. 330200
OUT = 50mAac
IN = 25Aac
COD. 330201
OUT = 50mAac
80215G_MHW_800P_07-2021_ENG