Using a PT Controller: Setup
*
Hold CV Chg VDC – This setting holds the battery voltage at the CV Charge Volts set-
ting. This is for a system that requires a constant charge voltage to be present at all times
(see Figure 10-2).

Figure 10-2, Hold CV Charge Volts (PT Controller)

◊ Set Battery Type (Custom) – This selection allows you to individually adjust the fl oat,
absorb, and equalization charge voltage settings and to set an equalization time for your
batteries. This allows the multi-stage charging method (see Figure 10-3) to be customized
specifi cally for your batteries. Use the following Custom battery settings to determine the bat-
tery's absorption, fl oat, and equalization voltages, and the maximum amount of time spent
equalizing.
 Set Absorb Volts – Sets the level at which the charging voltage is held constant during
the Absorption charge.
Default: 14.4V (12v), 28.8V (24v), 57.6V (48v)
Range: 12.0-16.6V (12v), 24.0-33.2V (24v), 48.0-66.4V (48v)
 Set Float Volts – Sets the level at which the charging voltage is held constant during
the Float charge.
Default: 13.2V (12v), 26.4V (24v), 52.8V (48v)
Range: 12.0-16.6V (12v), 24.0-33.2V (24v), 48.0-66.4V (48v)
 Set EQ Volts – Sets the level at which the charging voltage is held constant during the
Equalization charge.
Note: The EQ Volts setting cannot be set lower than the Absorb Volts setting, or more than
2 volts (12v systems), 4 volts (24v systems), or 8 volts (48v systems) above the Absorb
Volts setting.
Default: 15.6V (12v), 31.2V (24v), 62.4V (48v)
Range: 12.0-16.6V (12v), 24.0-33.2V, 48.0-66.4V (48v)
 Set EQ Done Time – Sets the time (duration) the battery charges at the EQ Volts setting.
Default: 4.0 Hrs
Range: 0.1-25.5 Hrs
Info: The internal timer for the EQ Done Time setting counts when the battery voltage
is equal to the EQ Volts setting, and clears when the controller status goes to Float
Charging. It clears automatically when the EQ charging fi nishes, or can be manually
cleared by selecting Float Start (under the CTRL: 04A PT CHG Ctrl menu).
Page 105