Electrical Supply Requirements

You will need a dedicated 120V 10 amp grounded
electrical service. The power supplied to your grill
enclosure must be on a dedicated circuit with no other
appliances or lights sharing the power.
You do not need to hire a contractor to install your
electrical service, but you must ensure you have
all required permits and the installation complies
with State and local code. We recommend you hire
a certified contractor if you do not wish to do the
installation yourself.
If your dealer is not a certified contractor, you will need
to hire a contractor for installation of your electrical
service.
When installed in the United States, the electrical
wiring must meet the requirements of National Electric
Code, ANSI/NFPA 70-1999 and any applicable state
or local codes. The electrical circuit must be installed
www.cal amebbq.com
by an electrical contractor and approved by a local
building / electrical inspector.
To determine the current, voltage, and wire size
required for the island configuration to be connected,
refer to the following:
Wire size is determined by length of run from
breaker box to the barbecue island and maximum
current draw.
We recommend copper wire with THHN insulation.
All wiring must be copper to ensure adequate
connections. Do not use aluminum wire.
When NEC requires the use of wires larger than #6
(10mm²), install a junction box near the barbecue
island and use #6 (10mm²) wire between the
junction box and the grill enclosure.