Screen Vents

Enclosure Ventilation

Note: This section describes ventilation within the grill enclosure itself and not ventilation for the barbecue
island.
Minimum
For proper ventilation, the base structure must be constructed using one of two designs:
Clearance
1
An enclosure with one side open
2
An enclosure having four sides, a top, and bottom
At least two ventilation openings at cylinder valve
level shall be provided in the side wall, equally sized,
spaced at 180 degrees and unobstructed.
Each opening shall have a total free area of not less
than 10 square inches (254 square mm).
Ventilation openings shall be provided at floor level
and shall have a total free area of not less than 10
square inches (254 square mm). If the ventilation
openings at floor level are in a side wall, there shall
Convection Grills
LTR50001038, Rev. J
Screen Vents
be at least two openings. The bottom of the openings
shall be at floor level and the upper edge no more
than 5 inches (127mm) above the floor. The openings
shall be equally sized, spaced, and unobstructed.
LP-gas cylinders should be ventilated by openings
at the level of the cylinder valve and the floor level.
The effectiveness of the openings, for purposes of
ventilation, shall be determined with the LP-gas supply
cylinder in place.