HR6S-AK
Safety Relay Module
Connects to pressure-sensitive switches such as mat switches
• Protects both the operator and the machine by immediately stopping
dangerous movements when instructed to stop by the operator or or
when a failure in the safety circuit is detected.
• Connects to pressure-sensitive switches such as mat switches or edge switches.
• NC contact is availalabe for output.
HR6S-AK
Terminal
Part No.
HR6S-AK1C
Push-in terminal
Screw terminal
HR6S-AK1P
One sealing strip (see page 28) is included with each product.
-
Overview of Application Functions
Monitoring of Emergency
Stop circuits as per ISO
13850 and IEC 60204-1,
stop category 0
Monitoring of guards as
per ISO 14119/14120
with interlock switches
Safety-Related Outputs
Number of relay contacts, Normally Open, instantaneous
Number of relay contacts, Normally Closed, instantaneous
Maximum short circuit current IK
Maximum continuous current, Normally Open relay contacts
Maximum continuous current, Normally Closed relay contacts 3 A
Maximum total thermal current ∑I
THERM
Minimum current
Utilization category as per UL 60947-5-1
Utilization category as per IEC 60947-4-1 and IEC 60947-5-1
Maximum current, normally open relay contacts
Maximum current, normally closed relay contacts
External fusing
Additional Non-Safety-Related Outputs
Output voltage
Maximum current
Synchronization Times
The synchronization times for the synchronization of safety-related
inputs depend on the application function. (See page
Selector and Input Device Connection Example.)
12
• See website for details on
TÜV NORD Systems
GmbH & Co.KG
approvals and standards.
Package Quantity: 1
Supply Voltage
24V AC/DC
24V AC/DC
Monitoring of guards as
per ISO 14119/14120
with coded magnetic
switches
Monitoring of proximity
switches
2
1
1 kA
6 A
12 A
10 mA
B300 and R300 for
Normally Open contacts
D300 and R300 for
Normally Closed contacts
AC-1: 250 V
AC-15: 250 V
DC-1: 24 V
DC-13: 24 V
AC-1: 5 A
AC-15: 3 A
DC-1: 5 A
DC-13: 3 A
AC-1: 3 A
AC-15: 1 A
DC-1: 3 A
DC-13: 1 A
10 A, category gG, for
Normally Open
4 A, category gG, for
Normally Closed
24V DC
20 mA
13
Function Mode
Monitoring of electro-sensitive
protective equipment such as
type 4 light curtains as per IEC
61496-1
Monitoring of RFID
sensors
Data Functional Safety
Defined safe state
Maximum Performance Level (PL), Category
(as per ISO 13849-1:2015)
Maximum Safety Integrity Level (SIL)
(as per IEC 61508-1:2010)
Safety Integrity Level Claim Limit (SILCL)
(as per IEC 62061:2005+AMD1:2012+AMD2:2015)
Type (as per IEC 61508-2)
Hardware Fault Tolerance
(HFT) (as per IEC 61508 and IEC 62061)
Stop Category for Emergency Stops
(as per ISO 13850 and IEC 60204-1)
Lifetime in years at an ambient temperature of 55 °C
(131 °F)
Safe Failure Fraction (SFF)
(as per IEC 61508 and IEC 62061)
Probability of Dangerous Failure per hour (PFH
(as per IEC 61508 and ISO 13849-1)
Mean Time To Dangerous Failure (MTTF
) in years
D
(as per ISO 13849-1)
Average Diagnostic Coverage (DC
)
avg
(as per ISO 13849-1)
DC-13
Maximum number of cyclesover lifetime
AC-1
AC-15
*1) According to ISO 13849-1 Annex K
For other specifications (common to all models), see page 27.
Output expansion
possible
Monitoring of pressure-
sensitive 4-wire
protective devices
such as mats or edges
as per ISO 13856
Safety-related outputs are de-
energized
Normally Open: open
Normally Closed: closed
Normally Open: PL e, Category 4
Normally Closed: PLc, Category 1
Normally Open: 3
Normally Closed: 1
Normally Open: 3
Normally Closed: 1
B
1
0
20
>99 %
) in 1/h
D
1.13 x 10
-9
2,000 (*1)
≥99 %
24V DC 1 A: 1,200,000
24V DC 3 A: 180,000
250V AC 4 A: 180,000
250V AC 1 A: 70,000
250V AC 5 A: 39,000