Medium's evaporation temperature

Speed control

Pump speed
min / max

Yield measurement

Antifreeze
Pump capacity
128/221
Siemens Switzerland Ltd
HVAC Products
T
Tkol
TSpSi
TSp
On
Off
TSpSi
Storage tank safety temperature
TSp
Storage tank temperature
TKolUe
Collector temperature for overtemperature protection
TSpmax Maximum charging temperature
Tkol
Collector temp
On / Off Collector pump
T
Temperature
t
Time
Line no.
Operating line
3860
Evaporation heat carrier
If there is a risk of the heat-carrying medium evaporating due to high collector
temperatures, the collector pump is deactivated to prevent overtemperatures. This is a
protective pump function.
Line no.
Operating line
3870
Pump speed min
3871
Pump speed max
The speed range of the solar pump is limited by the minimum and maximum
permissible speed.
Line no.
Operating line
3880
Antifreeze
3881
Antifreeze concentration
3884
Pump capacity
The 24-hour and total solar energy yield (8526 and 8527) is calculated, based on these
data.
Since the mixing ratio of the collector medium has an impact on heat transmission, the
type of antifreeze used and its concentration must be entered in order to be able to
determine the energy yield.
The flow rate in l/h of the pump used must be determined and serves for calculating the
volume delivered.
User manual RVS61.843
6 The settings in detail
1°C
TSp
TSpMax
TKolUe
1°C
t
CE1U2355en_02
23. November 2007