Charging controller solar (dT)

Siemens Switzerland Ltd
HVAC Products

6.14 Solar

B61
B6
Q16
Q5
1
0
K18
When sufficient solar energy is available, it can be used to heat the swimming pool and
to charge the DHW and buffer storage tank. Priorities for heating or charging can be
selected. The pumps can be speed-controlled. The plant is protected against frost and
overtemperatures.
Line no.
Operating line
3810
Temp diff on
3811
Temp diff off
3812
Charg temp min DHW st tank
3815
Charging temp min buffer
3818
Charging temp min swi pool
To charge the storage tank / heat the swimming pool via the heat exchanger, an
adequate temperature differential between collector and buffer storage tank or
swimming pool, is required. In addition, the collector temperature must lie above the
minimum charging temperature for the storage tank / swimming pool.
T
On
OFF
Tkol
Collector temp
On / Off Collector pump
SdOn
Temperature differential on
SdOff
Temperature differential off
TSp
Storage tank temperature
TLmin Charging temp min DHW storage tank / buffer / swimming pool
User manual RVS61.843
6 The settings in detail
B13
B4
B41
1
0
K8
Tkol
SdEin
SdAus
TSp
TLmin
t