Actuator type
Switching differential
2-pos
Actuator running time
Mixing valve in heating
mode

Dewpoint monitoring

Lock time dewpoint limiter
Flow temp setp incr hygro
Flow setp incr start at r.h.
Siemens Switzerland Ltd
HVAC Products
2-position
The controller drives the actuator with only one relay output. When the output delivers a
signal, the valve opens. When there is no signal, the valve closes automatically.
3-position
The controller drives the actuator with 2 relay outputs. One of the outputs is used for
opening the valve, the other for closing the valve.
For the 2-position actuator, the "2-position switching differential" must also be adapted.
The switching differential has no impact on 3-position actuators.
For the 3-position actuator, the running time of the mixing valve actuator can be
adjusted. The actuator running time has no impact on 2-position actuators.
This defines the position of mixing valve 1 (Y1 / Y2) when heating mode is active.
This parameter has no impact on systems with hydraulically separate heating and
cooling circuits.
The valve is used for control in heating and cooling mode.
Controls
The valve is used for control in cooling mode, it is open in heating
Open
mode.
Line no.
Operating line
946
Lock time dewpoint limiter
947
Flow temp setp incr hygro
948
Flow setp incr start at r.h.
950
Flow temp diff dewpoint
When the connected dewpoint limiter detects the formation of condensation, it closes
its contact, thereby deactivating cooling .
The "Lock time dewpoint limiter" set here starts running as soon as the contact
reopens. Cooling can only start after expiry of this locking time.
The dewpoint limiter must be assigned to one of the Hx inputs as a "Dewpoint limiter".
To prevent the formation of condensation due to excess indoor air humidity, a hygrostat
can be used to implement a fixed increase in the flow temperature . As soon as the
air humidity exceeds the value set on the hygrostat, the contact closes and the flow
temperature setpoint is increased by the amount set here.
The hygrostat must be assigned to one of the Hx inputs as "Flow setp increase hygro".
To prevent the formation of condensation due to excess indoor air humidity, a DC
0...10 V humidity measurement can be used to implement a continuous increase in
the flow temperature .
If the relative humidity in the room exceeds the value defined by "Flow setp incr start at
r.h." the flow temperature setpoint is increased continuously. The start of increase (949)
and the maximum increase (947) can be set.
The humidity sensor must be assigned to one of the Hx inputs as "Rel room humidity
10V".
User manual RVS61.843
6 The settings in detail
93/221