Mounting method

Connections

Radio link

Establishing the link
Testing
32/221
Siemens Switzerland Ltd
HVAC Products
3.8.4

RF repeater AVS14.390

• To establish the radio link, the device must be temporarily connected to power prior
to mounting, enabling the radio link to be opened and tested
• The RF repeater must be fitted inside the building
1
2
Power is supplied via the enclosed power pack. The wires are interchangeable.
Make the radio connection in the vicinity of the RF module prior to mounting so that all
system components are within easy reach.
Prerequisite for the radio link is that all components receive power, which means that
the RF module must be correctly connected to the basic unit and power must be
correctly supplied to the RF repeater.
1.
Press the button on the RF module for at least 8
seconds until the LED on the radio module starts
blinking at high frequency.
2.
Press the button on the installed RF repeater until
the LED start blinking at high frequency.
3.
The connection is established when the LED on
the RF module extinguishes.
The test is made to check the quality of the radio link.
• The test can be aborted by pressing the ESC button
• While the radio link can be opened on the controller, the test should be made at the
location where the room unit will be installed
1.
Press button 3 on the RF repeater for a maximum of 8 seconds until the LED
starts blinking at low frequency.
2.
When radio communication works correctly, the LED on the RF module flashes
briefly at 10-second intervals.
3.
After the test, press the button on the RF repeater again briefly until the LED
extinguishes.
User manual RVS61.843
3 Mounting and installation
4
LED
Button
CE1U2355en_02
23. November 2007