Same interface and controller terminals are used for QMX3 room sensors P30, P40 and P70 connection.
Air Handling unit can be connected to the Building Management System via BACnet IP or Modbus (RS485).
BACnet Vendor Name: Siemens Building Technologies
Default BACnet/IP port: 47808 (0xBAC0)
Default Device Object Instance number: 1
Baudrate: 19200 bps
Data: 8 Bit
Parity: Even
Stop bit: 1
Slave address: 1
Figure 8.9.1.
Air quality sensor, remote controller and BMS connection to the S300 controller
"ACCESSORIES
SETUP (VERSION S300)".
for Modbus TCP/IP connection (see section "CONNECTION TO WIRING TERMINALS (VERSION S300)" for location of the Port2).

8.10. CONNECTION OF REMOTE CONTROL PANEL OR MODBUS (VERSION 1.1 / 1.2)

Wiring diagram.
Automation controller F zone, X18 connector.
Switch
Position
Purpose
S2
1
8.11. FIREPLACE PROTECTION/SYSTEM MODE SWITH/RAPID VENTILATION SWITCH INPUT
(VERSION S300)
1. Fireplace protection;
40
| EN
SMARTY v2023.1