Appendix A Wire The 5700 To The 3100 Relays - Emerson Micro Motion 5700 Installation Manual

Ethernet transmitters
Hide thumbs Also See for Micro Motion 5700:
Table of Contents

Advertisement

Installation Manual
MMI-20029768
A 
Wire the 5700 to the 3100 relays
Use this procedure to wire the Discrete Output on the 5700 Ethernet transmitter to the
3100 transmitter relays for single-stage batch control.
Prerequisites
Set up the Channel configuration to DO before wiring.
Use active high and internal power.
Use wire size 24 AWG (0.205 mm
Procedure
1. Wire the negative terminal on Channel from the 5700 Ethernet transmitter to A14.
2. Wire the positive terminal on Channel from the 5700 Ethernet transmitter to either
Installation Manual
C14, C16, or C18.
Figure A-1: Wiring for 5700 Ethernet Channel DO to 3100 relays
K3
K2
A
J 3
F3
T5A 250V
F2
DS3
C
A
DISC
OUT 3
IEC 127-2
IEC 127-2
2
) to 16 AWG (1.31 mm
K1
B
C
J 2
T5A 250V
F1
T5A 250V
DS2
C
A
DISC
OUT 2
IEC 127-2
Wire the 5700 to the 3100 relays
February 2023
2
).
A14
C18
C16
C14
J 4
J 1
DS1
C
A
DISC
OUT 1
55

Advertisement

Table of Contents
loading

Table of Contents