5700 Transmitters In Ethernet Networks - Emerson Micro Motion 5700 Installation Manual

Ethernet transmitters
Hide thumbs Also See for Micro Motion 5700:
Table of Contents

Advertisement

Planning
February 2023
R: cable resistance
L: cable length (in Ω/ft)
Typical power cable resistance at 68 °F (20.0 °C)
Wire gauge
14 AWG
16 AWG
18 AWG
20 AWG
2.5 mm
1.5 mm
1.0 mm
0.75 mm
0.50 mm
2.3.1 
Maximum cable lengths between sensor and transmitter
The maximum cable length between the sensor and transmitter, which are installed
separately, is determined by cable type.
Cable type
Micro Motion 4-wire remote
mount
Micro Motion 9-wire remote
mount
User-supplied 4-wire
(1)
For Smart Meter Verification, the limit is 60 ft (18 m).
2.4 

5700 transmitters in Ethernet networks

You can install the 5700 Ethernet transmitter in star, ring, or daisy-chain networks using
industrial-rated shielded Ethernet cables.
Make sure that each cable is no longer than 328 ft (100 m).
Connect the 5700 Ethernet transmitter to the host system via a LAN (Local Area
Network) and not a WAN (Wide Area Network).
Follow all network security best practices.
10
2
2
2
2
2
Wire gauge
Not applicable
Not applicable
VDC 22 AWG (0.326 mm²)
VDC 20 AWG (0.518 mm²)
VDC 18 AWG (0.823 mm²)
RS-485 22 AWG (0.326 mm²) or
larger
Resistance
0.0050 Ω/ft
0.0080 Ω/ft
0.0128 Ω/ft
0.0204 Ω/ft
0.0136 Ω/m
0.0228 Ω/m
0.0340 Ω/m
0.0460 Ω/m
0.0680 Ω/m
Maximum length
1,000 ft (305 m) without Ex-
approval
500 ft (152 m) with IIC rated
sensors
1,000 ft (305 m) with IIB
rated sensors
1,000 ft (305 m)
300 ft (91 m)
500 ft (152 m)
1,000 ft (305 m)
1,000 ft (305 m)
Micro Motion 5700 Ethernet Transmitters
Installation Manual
MMI-20029768
(1)

Advertisement

Table of Contents
loading

Table of Contents