Temperature converter with trip relays KF**-GUT-(Ex)1.D
Editing devide data: Current output

8.6.3 Start value and final value

Be aware of the following when entering the start value and the final value:
The following rule applies if the assignment Ch1 has been selected (see section 8.6):
− Both values must be specified in the unit selected under Unit (see section 8.3).
− The input limits depend on the maximum measuring range of the selected sensor (see section
8.9). The difference between the final value and the start value must be at least 1 % of the start
value (automatically predefined by the GUT).
The following rule applies if the assignment Trend has been selected (see section 8.6):
− Both values must be specified as unit/sec. (e.g. °C/sec).
− For all units except for mV, the start value can be selected from -100 unit/sec to +99.00 unit/
sec ; for mV it can be selected from -10.0 mV/sec to
+9.900 mV/sec. A final value in the range between the start value + 1% and +100.0 unit/sec or
+10.00 mV/sec can be selected.
Subject to reasonable modifications due to technical advances.