8.6.2 Interference current

The following table shows what the result of the current output is depending on the setting in the event
of a malfunction:
Setting
Min
Max
hold
Up/down
only useful
for RTD
The current output behaviour in case of the various alarm indications regarding a redundant
thermocoupler is described in section 8.2.4.
Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Temperature converter with trip relays KF**-GUT-(Ex)1.D
Current path
characteristic
0 ... 20 mA
0 mA
(cannot be distinguished
from the measurement of
the start value)
approx. 21.5 mA
last measured value before fault occurred
0 mA
for Err SB
(cannot be distinguished
from a measurement of
the start value)
approx. 21.5 mA
for Err SC
Editing devide data: Current output
Characteristics
4 ... 20 NE43,
4 ... 20 mA (b)
2.0 mA
approx. 21.5 mA
2.0 mA
for Err SB
approx. 21.5 mA
for Err SC
Characteristic
4 ... 20 mA
0 mA
(cannot be distinguished
from an underrange of the
start value)
approx. 22 mA
(cannot be distinguished
from a final value
overrange)
0 mA
for Err SB
(cannot be distinguished
from an underrange of the
start value)
approx. 22 mA
for Err SC
(cannot be distinguished
from an overrange of the
final value)