Basic Functions; Changing The Operating State, Automatic, Manual - Burkert 3320 Quick Start Manual

Electromotive 2/2-way valve
Table of Contents

Advertisement

Available languages

Available languages

Type 3320, 3321

Basic functions

10.2.1 DIP switch
Settings
Switch 1:
Activate or deactivate safety position see
chapter "11" on page 37.
Switch 2:
Select safety position between NO and NC see
chapter "11" on page 37.
Switch 3:
Not used.
Switch 4:
Switch between AUTOMATIC and MANUAL
operating state.
See chapter "11.1" on page 37.
10.2.2 OPEN button and CLOSE button
Electrical manual override:
Trigger X.TUNE (Autotune):
10.2.3 Mechanical manual override
If there is no supply voltage, e.g. during installation or in the
event of a power failure, the valve can be opened or closed using
the mechanical manual override.
For a description see chapter "12.2 Actuating the valve
mechanically"
Opening valve: Press OPEN
button
Closing valve: Press CLOSE
button
For a description see chapter "9.4
Adjustment of position controller –
execute X.TUNE".
11
BASIC FUNCTIONS
The basic functions are set using the DIP switch position.
DIP switch
Basic function
Enable or disable
1
safety setting
Set safety setting
and effective
2
direction (NC and
NO)
3
Not used
Switch between
AUTOMATIC and
4
MANUAL operating
state.
Tab. 18: Overview of basic functions
11.1
Changing the operating state,
AUTOMATIC, MANUAL
Factory setting: Devices in their factory default state have their
operating state preset to MANUAL.
DIP switch 4, which is located under the blind cover, is used to
change operating state.
English