5.2 Troubleshooting

If troubleshooting, check the fault by using the Hand Held Communicator (HHC) with function
"SELF CHECK" - Refer the chapter " Operation" in this manual.
The transmitter is supplied with the burnout adjusted : "fixed" output signal in case of
failure.
If an abnormality occurred in the process or transmitter, action should be taken with
references to the table below:
Symptom
Output current
overshoots
scale
(The value is
more than the
upper limit of
the saturation
current.).
No output
current (The
value is less
than the lower
limit of the
saturation
current.).
Output current
error.
When the
indicator is
abnormal.
If remedy is impossible, contact Fuji Electric's service department.
INF-TN5FCXA2V5e-E
Cause
(1) The manifold valve does not open/
close normally.
(2) Pressure leak is occurring.
(3) Process piping is improper.
(4) Process pipe is clogged.
(5) Power supply voltage and/or load
resistance is improper.
(6) Voltage between the external
unit is wrong.
current(4, 20mA) are not adjusted.
(1) Same as (1) to (4) above
(2) Power supply polarity is wrong.
(3) Power supply voltage and/or load
resistance is improper.
(4) Voltage between the external
connection terminals is wrong.
current(4, 20mA) are not adjusted.
(1) Process piping is improper.
(2) Gas or solution is mixed in.
(3) Liquid density changes.
(4) Ambient temperature changes
widely.
(4, 20mA) has deviated.
(1) An error display is appeared.
Remedy
Repair the valve so that it opens/closes normally.
Repair a leak.
Make correct piping.
Eliminate the cause of clogging.
Make arrangement to obtain proper values. For
power supply voltage and load resistance, refer to
chapter 7.2.
(For intrinsically safe installations, the power
supply voltage should be 16.1 to 26V DC.)
Check for faulty cable, insulation, etc. and repair
as needed.
For power supply voltage and load resistance,
refer to chapter 7.2.
(For intrinsically safe installations, the power
supply voltage should be 16.1 to 26V DC.)
Readjust according to chapter 4.
Correct wiring according to chapter 7.1.
Make arrangement to obtain proper values.
(For power supply voltage and load resistance,
refer to chapter 7.2.)
(For intrinsically safe installations, the power
supply voltage should be 16.1 to 26V DC.)
Check for faulty cable, insulation, etc. and repair
as needed.
(For power supply voltage and load resistance,
refer to chapter 7.2.)
(For intrinsically safe installations, the power
supply voltage should be 16.1 to 26V DC.)
Readjust according to chapter 4.
Correct the piping.
Vent or drain the transmitter.
Perform density compensation.
Minimize the temperature change.
Readjust according to chapter 4.
P28 capital to "contents of message"
69