(3) Operating condition setting completed flag (X9)
When changing the following settings, use Operating condition setting completed flag (X9) as an interlock
condition to turn Operating condition setting request (Y9) OFF → ON → OFF.
• A/D conversion enable/disable setting (Un\G0)
• CH
Average time/Average number of times/Move average settings (Un\G1 to Un\G4)
• Averaging process specification (used to replace Q64AD) (Un\G9)
• Averaging process specification (Un\G24)
• Conversion speed setting (Un\G26)
• Input signal error detection setting (Un\G47)
• Process alarm output setting (Un\G48)
• Scaling enable/disable setting (Un\G53)
• CH
Scaling lower limit value (Un\G62, Un\G64, Un\G66, Un\G68)
• CH
Scaling upper limit value (Un\G63, Un\G65, Un\G67, Un\G69)
• CH
Process alarm lower lower limit value (Un\G86, Un\G90, Un\G94, Un\G98)
• CH
Process alarm lower upper limit value (Un\G87, Un\G91, Un\G95, Un\G99)
• CH
Process alarm upper lower limit value (Un\G88, Un\G92, Un\G96, Un\G100)
• CH
Process alarm upper upper limit value (Un\G89, Un\G93, Un\G97, Un\G101)
• CH
Input signal error detection setting value (Un\G142 to Un\G145)
When Operating condition setting completed flag (X9) is OFF, the A/D conversion processing is not executed.
In the case of the following status, Operating condition setting completed flag (X9) turns OFF.
• When Operating condition setting request (Y9) is ON
Module READY (X0)
Operating condition setting
completed flag (X9)
Operating condition setting
request (Y9)
A/D conversion completed
flag (XE)
96
Controlled by the A/D converter module
Controlled by the program
ON
ON
ON
ON
ON
OFF
OFF
ON
OFF