Mitsubishi MELSEC-L Series User Manual page 112

Analog-digital converter module
Hide thumbs Also See for MELSEC-L Series:
Table of Contents

Advertisement

(19)CH
Process alarm lower lower limit value (Un\G86, Un\G90, Un\G94, Un\G98),
CH
Process alarm lower upper limit value (Un\G87, Un\G91, Un\G95, Un\G99),
CH
Process alarm upper lower limit value (Un\G88, Un\G92, Un\G96, Un\G100),
CH
Process alarm upper upper limit value (Un\G89, Un\G93, Un\G97, Un\G101)
Set the digital output value range for each channel.
For details on warning output function (process alarm), refer to the following.
• Warning Output Function (Process Alarm) (
(a) Setting range
• Setting range is -32768 to 32767.
• Configure the 4-step setting of process alarm upper upper limit value, process alarm upper lower limit
value, process alarm lower upper limit value and process alarm lower lower limit value.
(b) Enabling the setting
Turn OFF → ON → OFF Operating condition setting request (Y9) to enable the setting.
(c) Default value
0 is set as the default value.
● When a value out of the setting range above or a value which does not satisfy the formula of process alarm upper upper
limit value ≥ process alarm upper lower limit value ≥ process alarm lower upper limit value ≥ process alarm lower lower
limit value is set to a channel, an error occurs in the channel. The error code is stored in Latest error code (Un\G19), and
Error occurrence flag (XF) is turned to ON. The operation is performed in the setting configured before the error
occurrence.
● Change the setting value, since 0 is set as the default value.
● When Scaling enable/disable setting (Un\G53) is "enable", be sure to set a value considering the scale conversion.
110
Page 56, Section 8.7)