Mitsubishi MELSEC-L Series User Manual page 44

Analog-digital converter module
Hide thumbs Also See for MELSEC-L Series:
Table of Contents

Advertisement

Item
A/D conversion enable/disable
setting
Averaging process specification
Basic setting
Average time/Average number of
times/Move average settings
Conversion speed setting
Process alarm output setting
Process alarm upper upper limit
Warning output
value
function
Process alarm upper lower limit value -32768 to 32767 (default value: 0)
Process alarm lower upper limit value -32768 to 32767 (default value: 0)
Process alarm lower lower limit value
Input signal error detection setting
Input signal error
detection
Input signal error detection setting
value
Scaling enable/disable setting
Scaling function
Scaling upper limit value
Scaling lower limit value
42
Setting value
0: Enable (default value)
1: Disable
0: Sampling Processing (default value)
1: Time Average
2: Count Average
3: Moving Average
20µs: 2 to 1500ms (default value: 0)
Average time
80µs, 1ms: 2 to 5000ms (default value: 0)
Average
number of
4 to 62500 times (default value: 0)
times
Move
average
2 to 1000 times (default value: 0)
settings
0: 20µs
1: 80µs (default value)
2: 1ms
0: Enable
1: Disable (default value)
-32768 to 32767 (default value: 0)
-32768 to 32767 (default value: 0)
0: Enable
1: Disable (default value)
0 to 25.0% (default value: 5.0%)
0: Enable
1: Disable (default value)
-32000 to 32000 (default value: 0)
-32000 to 32000 (default value: 0)
Reference
Page 48,
Section 8.2
Page 48,
Section 8.3
Page 52,
Section 8.4
Page 56,
Section 8.7
Page 53,
Section 8.6
Page 59,
Section 8.8