Mitsubishi MELSEC-L Series User Manual page 65

Analog-digital converter module
Hide thumbs Also See for MELSEC-L Series:
Table of Contents

Advertisement

2. When a 17th error occurs:
Ex.
The 17th error is stored in error history No.1, and the value "1810" (start address of error history No.1) gets stored to
Latest error code address (Un\G1800).
Latest error code address
(Un\G1800)
● The same process for errors is used when an alarm occurs.
● Once the error history storage area becomes full, subsequent errors will overwrite the previous errors, starting from error
history No.1, and continues sequentially thereafter (Un\G1810 to Un\G1819). (The overwritten history is deleted.)
● The stored error history is cleared when power supply is turned OFF, or when the CPU module is reset.
Address
1810
Error history No.1
1st error
1820
Error history No.2
2nd error
1830
Error history No.3
3rd error
1960
Error history No.16
16th error
CHAPTER 8 FUNCTIONS
New
17th error
The 17th error is stored in Error history
No.1 and the 1st error history will be erased.
8
63