Mitsubishi MELSEC-L Series User Manual page 105

Analog-digital converter module
Hide thumbs Also See for MELSEC-L Series:
Table of Contents

Advertisement

(3) Averaging process specification (used to replace Q64AD) (Un\G9)
Write the setting for averaging processing when using the sequence program for initial setting of the Q64AD.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5
0
0
(a) Enabling the setting
To enable the setting, turn OFF → ON → OFF Operating condition setting request (Y9) after setting Averaging
process specification (Un\G24) to sampling processing (0).
When selecting the moving average, it is necessary to write 0 to Averaging process specification (used to replace Q64AD)
(Un\G9), and write the moving average to Averaging process specification (Un\G24).
(b) Default value
All channels are set to sampling (0) as the default value.
(4) A/D conversion completed flag (Un\G10)
A/D conversion status can be checked with this flag.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5
0
0
0
Data for b4 to b15 are fixed to "0".
(a) A/D conversion completion
When the first A/D conversion is completed in the channel where the A/D conversion is enabled, the flag is
turned to A/D conversion completion (1).
A/D conversion completed flag (XE) is turned to ON when the conversion of all the channels where the A/D
conversion is enabled are completed.
Turning OFF → ON → OFF Operating condition setting request (Y9) turns the flag to 0 (default value), and the
flag is turned to A/D conversion completion (1) when the first A/D conversion is completed.
When A/D conversion enable is set to CH1 and CH2 and all the A/D conversions in CH1 and CH2 are
Ex.
completed, 0003
(3) is stored in A/D conversion completed flag (Un\G10), as shown below.
H
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5
0
0
0
0 CH4 CH3 CH2 CH1 0
Averaging processing channel specification
1: Averaging processing
0: Sampling processing
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
b4
b3
b2
b1
b0
0
0
0
CH4
CH3
CH2
CH1
Time/number of times specification
1: Time
0: Number of times
b4
b3
b2
b1
b0
0
0
CH4
CH3
CH2
CH1
1: Conversion completed
0: During conversion or unused
b4
b3
b2
b1
b0
0
0
0
0
0
1
1
CH4
CH3
CH2
CH1
0