(4) Example of scaling setting
1. When setting the "Scaling upper limit value" to "16000" and the "Scaling lower limit value" to "4000" for a
Ex.
channel with input range of 0V to 5V:
The digital output values and scaling values are as follows:
Scaling upper limit value 16000
Scaling lower limit value 4000
Analog input voltage (V)
0
1
2
3
4
5
2. When setting the "Scaling upper limit value" to "16000" and the "Scaling lower limit value" to "4000" for a
Ex.
channel with input range of -10V to 10V:
The digital output values and scaling values are as follows:
Scaling upper limit value 16000
Scaling lower limit value 4000
Analog input voltage (V)
-10
-5
0
5
10
Digital output value
20000
0
0
5
Digital output value
0
4000
8000
12000
16000
20000
Digital output value
20000
-20000
-10
0
10
Digital output value
-20000
-10000
0
10000
20000
CHAPTER 8 FUNCTIONS
Analog input voltage (V)
Scaling value
4000
6400
8800
11200
13600
16000
Analog input voltage (V)
Scaling value
4000
7000
10000
13000
16000