Mitsubishi MELSEC-L Series User Manual page 106

Analog-digital converter module
Hide thumbs Also See for MELSEC-L Series:
Table of Contents

Advertisement

(5) CH
Digital output value (Un\G11 to Un\G14)
The A/D-converted digital output value is stored as a signed 16-bit binary value.
(a) Updating cycle
When performing the average processing, the value is updated in each specified averaging processing cycle.
When the average processing is not performed, the value is updated in each sampling cycle.
(6) Latest error code (Un\G19)
Error codes or alarm codes detected in the A/D converter module are stored.
For details on error code and alarm code, refer to the following.
• Error code list (
• Alarm code list (
(a) Clearing an error
Turn OFF → ON → OFF Error clear request (YF).
(7) Setting range (Un\G20)
The setting content for input range can be checked.
Setting range of A/D converter module
The setting cannot be changed with Setting range (Un\G20).
For changing the setting, refer to the following.
● Switch setting (
104
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5
Sign bit
1: Negative
2: Positive
Page 89, Section 11.4)
Page 91, Section 11.5)
b15
to
b12 b11
to
CH4
CH3
Input range
4 to 20mA
0 to 20mA
1 to 5V
0 to 5V
-10 to 10V
0 to 10V
User range setting
Page 40, Section 7.2)
b4
b3
b2
Data section
b8 b7
to
b4
b3
CH2
b1
b0
to
b0
CH1
Setting value
0
H
1
H
2
H
3
H
4
H
5
H
F
H