Mitsubishi MELSEC-L Series User Manual page 60

Analog-digital converter module
Hide thumbs Also See for MELSEC-L Series:
Table of Contents

Advertisement

(6) Setting procedure
1.
Set "A/D conversion enable/disable setting" to "0: Enable".
Project window
2.
Set "Process alarm output setting" to "0: Enable".
3.
Specify the values for "Process alarm upper upper limit", "Process alarm upper lower limit value",
"Process alarm lower upper limit value", and "Process alarm lower lower limit value".
Process alarm upper upper limit value
Process alarm upper lower limit value
Process alarm lower upper limit value
Process alarm lower lower limit value
Process alarm output settings must meet the following condition:
Process alarm upper upper limit value ≥ Process alarm upper lower limit value ≥ Process alarm lower upper limit value ≥
Process alarm lower lower limit value
58
[Intelligent Function Module]
Item
module name
Setting range
-32768 to 32767
[Parameter]