(3) Detection cycle
When time average is specified, the function is executed per set time (for averaging). When count average is
specified, the function is executed per set count (for averaging).
In addition, when sampling processing and moving average processing are specified, the function is executed per
sampling time.
(4) Clearing the alarm code
After the digital output value returns within the setting range, turn Error clear request (YF) OFF → ON → OFF.
This clears the alarm code 10
(5) If the scaling function is enabled
If Scaling enable/disable setting (Un\G53) is set to "Enable", the alarm output function monitors CH
value (Un\G54 to Un\G57) for alarm output.
When setting CH1 Process alarm lower lower limit value (Un\86) through CH4 Process alarm upper upper limit
value (Un\G101), make sure to specify values that reflect scale conversion.
Item
Scaling enable/disable setting
(Un\G53)
, which was stored in Latest error code (Un\G19).
Digital values monitored for alarm output
0: Enable
CH
Scaling value (Un\G54 to Un\G57)
1: Disable
CH
Digital output value (Un\G11 to Un\G14)
CHAPTER 8 FUNCTIONS
Scaling
57